Operational considerations, Troubleshooting – ADC P-80-412 User Manual

Page 7

Advertising
background image

ADCP-80-412

N Issue 1 N April 2000

Page 7

© 2000, ADC Telecommunications, Inc.

TOP VIEW

FRONT VIEW

LEFT SIDE VIEW

RIGHT SIDE VIEW

POWER

CONNECTOR

SENSOR

CONNECTOR

RED

FLASHING

LED

13928-B

Figure 5. Bay Tracer Electronic Sensor Device Connectors

5. Attach the customer-supplied power feed wires for the electronic sensor device to an

unused –48 Vdc branch circuit on the DSX-1 or DSX-3 fuse panel as shown in

Figures 3

and

4

. Attach the opposite ends of these wires to the ADC-provided power connector on

the electronic sensor device making sure that the wire supplying –48 Vdc is routed to the
–48V pin on the POWER receptacle and the battery return wire is routed to the RET pin
on the receptacle. See

Figure 5

. A reverse blocking diode is incorporated into the electronic

sensor device to prevent damage from a power lead reversal.

Note

: The fuse panel branch circuit should be fused at 0.5 A.