Operational considerations, Troubleshooting, Customer information and assistance – ADC P-80-412 User Manual

Page 8

Advertising
background image

ADCP-80-412

N Issue 1 N April 2000

Page 8
© 2000, ADC Telecommunications, Inc.

4 OPERATIONAL

CONSIDERATIONS

The electronic sensor device LED may be falsely activated by external EMI emitted by power
drills, wire wrap guns, or other AC powered devices located within 12 inches of the inductive
pick-up coil. If such a condition occurs, the electronic sensor device automatically resets after
the change in current state and returns to a constant dc state.

5 TROUBLESHOOTING

The LED on the bay tracer electronic sensor device is designed to light whenever an individual
jack LED is activated on a DSX bay configured with the device.

Table 2

provides a description

of common error conditions that may occur due to improper installation.

Table 2. Bay Tracer Troubleshooting

CONDITION

DESCRIPTION

Battery return conductor inserted into coil

LED activates when jack is removed

Labeled side of coil is facing away from the power
source

LED activates when jack is removed

Both –48 Vdc and battery return conductors are
inserted into the coil

Bay Tracer Illuminator does not function

–48 Vdc and battery return conductors are mis-wired
on POWER connector

Bay Tracer Illuminator does not function

Advertising