16

Remote Power-Off Device — Installation and Quick Start

Configuration and Setup: Set up the Remote Power-Off Device

Remote switch:
requirements
and pin
assignment

Pin locations for
the keystone
jack

Pin locations for
the RJ-11
connector

Type

Requirements

RPO/Cascade In
Pin Assignment

Contact
Closure

• Safety Extra Low Voltage

(SELV) or Class 2 circuit

• Switch or relay properly

isolated from the utility

• Latching

2 and 5

Voltage
Input

• SELV or Class 2 circuit
• Switched 24 V AC/DC
• Latching

3 and 4

1

4

6

2

5

3

2 3 4

5