Product Information

Selecting and Ordering Components

Remote switch
specifications

Cable
requirements

You can use the two RJ-11 cables that came with the Remote
Power-Off Device or use existing building cables. The cable
that connects the Remote Power-Off Device to the remote
switch must meet these requirements:

• It must be UL-listed
• Wire size must be 26 – 22 AWG
• Wire type must be one of the following:

– CL2: Class 2 cable for general use
– CL2P: Plenum cable for use in ducts, plenums, or

other space used for environmental air

– CL2R: Riser cable for use in a vertical run in a shaft

or from floor to floor

– CL2X: Limited-use cable for use in dwellings or in

raceway

For installations in Canada, the cable must be CSA certified,
type ELC (extra-low-voltage control cable).

Ordering
components

To order additional components, contact APC at a phone
number on the back cover of this manual or order online at the
American Power Conversion Web site, www.apc.com.

See “Remote switch: requirements and pin
assignment” on page 16
.

Warning

Incorrect installation can cause improper
functioning of the device or damage to hardware.
Substandard cables can produce toxic fumes if a
fire occurs.