Name of each part, Lonworks gateway – LG PQNFB16A1 User Manual

Page 10

Advertising
background image

Name of each part

10 Lonworks Gateway

Name of each part

1

2
3
4
5
6

7

8

BUS_A: 485 communication line A (+)

BUS_B: 485 communication line B (-)

F1, F2: Fire detection function (external device) contact point connection

LAN: LAN port necessary for web function

LON: TP/FT-10 communication line (Lonworks system communication line) non-polarity

PWR: Connection to DC 12V power adapter

12V: Connection when not using DC 12V power adapter

GND: Connection when not using GNS adapter

ALIVE/WINK: It flashes every 1 second when it is normal

It flashes 5 times when receiving WINK command from Lonworks system
(Green)

SERVICE: It is turned off when it is normal and flashes when it is not connected to the

Lonworks system. It is turned on when the service switch is pressed.

SERVICE SWITCH: When you press the switch the Neuron ID is transmitted to the

Lonworks system, and the service LED is turned on.

BNU-LW (PNF-B16A1) product is a product certified of LON-MARK, an international
standard. (Lon Mark Version 3.3)

1

8

2

3

4

5

6

7

LONWORKS GATEWAY

No. 6 and No. 7,8 are all for power supply. Therefore, only one of two combinations should be used.
When DC 12V is used for the power, Connect No. 6 to the power (not necessary to use No. 7,8.)
When DC 12V is NOT used for the power, Connect No. 7, 8 to the power (not necessary to use No. 6.)