22 Lonworks Gateway

Ventilation control/monitoring point

1

ON/OFF (setting)

SNVT_switch nviOnOff_nn

input

Stop

Operation

2

ON/OFF (status)

SNVT_switch nvoOnOff_nn

output

Stop

Operation

3

Lock (setting)

SNVT_switch nviLock_nn

input

Cancel

Setting

4

Lock (status)

SNVT_switch nvoLock_nn

output

Cancel

Setting

5

Operation Mode (setting)

SNVT_hvac_modenviHeatCool_nn

input

Auto

Heat exchange

Normal

6

Operation Mode (status)

SNVT_hvac_mode nviHeatCool_nn

output

Auto

Heat exchange

Normal

7

Fan speed(setting)

SNVT_switch nviFanSpeedCmd_nn

input

Low

High

Very high

8

Fan speed(status)

SNVT_switch nvoFanSpeed_nn

output

Low

High

Very high

9

Error Code

SNVT_hvac_status nvoUnitStatus_nn

output

Refer to the LG Air Conditioner Error Code.

10

User Mode(setting)

SNVT_count nviUser_nn

output

Quick

Power save

heat

11

User Mode(status)

SNVT_count nvoUser_nn

output

Quick

Power save

heat

Point

No.

Name

Object

Type

Unit

code 0

code 1

code 2

code 3

code 5

code 9

Object Name

(nn: Air conditioner and ventilation

group/indoor unit address)