Operating Instructions

70400101 (EN)

18

Ignition Control Operation for CE
Models

Power Up
After 24VAC is applied to the ignition control pins

24V and GND, the Diagnostic LED on the ignition

control will turn orange/yellow. If a fault is detected

the ignition control will enter Lockout Mode. If no

faults are detected, the Diagnostic LED will turn

Green and the ignition control will enter Standby

Mode.
Standby Mode
While in Standby Mode, the ignition control will

continually monitor the system for faults. Once

24VAC

is applied to terminals TH and GND on the

control, the ignition control will enter Start Up Mode.
Start Up Mode
During Start Up Mode, the ignition control will

monitor the system for faults and begin the ignition

sequence. If no faults are present, the ignition control

will begin the ignition sequence by entering an 18

second waiting period. During this time the Green

LED on the ignition control will switch between Red

and Green, before maintaining a Green color.
After the waiting period, the ignition control will turn

on the igniter and gas valve. The igniter will remain on

until a flame is sensed, or up to 10 seconds.
Once a flame has been sensed the ignition control will

stop sparking, the gas valve will remain on and

ignition control will enter Run Mode.
If a flame is not sensed, the ignition control will then

begin two additional retrials for ignition. The ignition

control will re-enter the 18 seconds waiting period

before the ignition control makes another attempt at

ignition. If the three attempts at ignition fail, the

ignition control will enter Lockout Mode.

Run Mode
While in Run Mode the ignition control leaves the gas

valve on, monitors the flame signal, and leaves the

igniter off.
If a flame signal is lost during Run Mode, one

additional retrial for ignition will take place within one

second. The ignition control will restore the spark for

approximately 10 seconds. If the ignition re-attempt

fails, the ignition control will enter Lockout Mode.
The ignition control will remain in Run Mode until

24VAC is removed from terminals TH and GND on

the control.
Termination of Flame
The flame will go out when power is removed from

ignition control. The ignition control will turn off the

gas valve and enter Standby Mode.
Lockout Mode
When Lockout Mode is entered, the ignition control

will remove power to the gas valve, the igniter will

turn off, the Lockout/Reset Light will turn on, and the

Diagnostic LED will display the appropriate Error

Code.
Lockout Manual Reset
Lockout Mode is cleared by pressing an external reset

switch for three seconds. The ignition control will

clear all error codes and enter Standby Mode. During

Lockout Manual Reset, the Diagnostic LED on the

ignition control flashes red and orange, and the Reset

Light remains on until the ignition control is reset.

After the Reset Light turns off, stop pressing the

switch. Holding the reset for three seconds after

lockout has been cleared will cause a fault and result in

entering Lockout Mode again.