Configuring the ups – HP Tower Uninterruptible Power System User Manual

Page 40

Advertising
background image

UPS operations 40

NOTE:

If the On and Off buttons are simultaneously pressed, the Off button has priority over

the On button.

Button

Assertion
time

Audible alarm Mode before

assertion

Utility
present ?

Action

On

0.5
seconds

Every 0.5
seconds until the
button is
released

Standby

Yes

Energizes the load and
resets the bypass entry
count to 0

Operate

Yes

Resets the bypass entry
count to 0

Auto-Bypass

Yes

Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode

Converter Off

Yes

Clears the UPS On audible
alarms, resets the bypass
entry count to 0, and
attempts to transfer to
Operate mode

Off

3 seconds

Every 0.5
seconds until the
button is
released

Operate

Yes

Transfers to Standby
mode, and power to the
load ceases

Standby

Yes

No action

Battery

No

Powers down the UPS, and
power to the load ceases

Auto-bypass

Yes or No

Transfers to Standby mode
or Converter Off mode,
and power to the load
ceases

Self Test

0.5
seconds

Any

Yes or No

Silences audible alarms
after 0.5 seconds

3 seconds

Continuously

Any

Yes or No

Initiates a self-test

Battery
Start

0.5
seconds

Any

Yes or No

No action

Battery
Start and
On

3 seconds

Continuously

UPS off

No

Transfers to battery power,
and begins powering the
load

On and
Self Test

3 seconds

Continuously

Any

Yes or No

Enters or exits
Configuration mode

Configuring the UPS

The UPS automatically detects the number of ERMs connected.