Power capping 45

----

718
The following example uses the power distribution module.
> show power pdm
PDM port 1

PDM Port Load

---- ---- ----

1 1 93 (AC watts)

1 2 140 (AC watts)

1 3 11 (AC watts)

1 4 228 (AC watts)

1 5 50 (AC watts)

----

522

PDM port 2

PDU: STI Serial TrueRMS PDU

Part Number: QL192A

Serial Number: ADFV0000083

Asset tag: SCI Lab PDU

Firmware rev: 1.0a

Infeed Amps: 60

Number of Infeeds: 4

Switched Outlets: 6

Infeeds:

01: Amps drawn: 0.850000 Status: On Load: Normal

02: Amps drawn: 0.880000 Status: On Load: Normal

03: Amps drawn: 0.820000 Status: On Load: Normal

04: Amps drawn: 2.560000 Status: N/A Load: Normal

Switched ports:

01: Enabled

02: Enabled

03: Enabled

04: Enabled

05: Enabled

06: Enabled
> show power 1 3
MDM Port Node Avg Min Max

---- ---- ---- ----- ----- -----

1 3 1 254 n/a 337 (DC watts)

1 3 2 255 n/a 340 (DC watts)

1 3 3 244 n/a 324 (DC watts)

1 3 4 233 n/a 315 (DC watts)

1 3 5 265 n/a 351 (DC watts)

1 3 6 258 n/a 344 (DC watts)

1 3 7 238 n/a 325 (DC watts)

1 3 8 259 n/a 346 (DC watts)

1 3 Fans 20 (DC watts)

1 3 2033 (Chassis total - DC watts)

1 3 2148 (Chassis total - AC watts)

1 3 2247 (Chassis cap - AC

watts)
Total servers = 8

Total chassis = 1

Total fan wattage = 20 (DC watts)