Notification window is not available on sles 10, On battery alarm, On boost alarm – HP Tower Uninterruptible Power System User Manual

Page 129: On buck alarm, Overload alarm, Receiving a security error

Advertising
background image

Troubleshooting 129

Notification window is not available on SLES 10

Symptom: The notification window does not appear on SLES 10.
Possible cause: This version of the operating system does not contain the required GTK 2.10 dependency for

notification functionality.
Action: Update to a SLES operating system that supports GTK 2.10.

On battery alarm

Action: The UPS continues to run on battery power until the battery is completely discharged (or until utility

power is restored), unless the shutdown parameters specify to power down all of the UPS load segments.

On boost alarm

Possible Cause: The input voltage is too low for the UPS. The UPS boosts the voltage up to acceptable limits.
Action: For information on Boost mode, refer to the UPS documentation.

On buck alarm

Possible Cause: The input voltage is too high for the UPS. The UPS bucks the voltage down to acceptable

limits.
Action: For information on Buck mode, refer to the UPS documentation.

Overload alarm

Possible Cause: The device load has exceeded the UPS power rating.
Action: Verify all equipment is drawing within the rated requirements. If necessary, reduce the equipment
connected to the UPS. The UPS might need to be reset.

Receiving a security error

Symptom: Security error: Domain Name mismatch message when trying to browse with SSL.
Possible Cause: The IP address or server name has changed.
Action: Stop the service, delete the certificate file, and restart the service.

Servers running Windows Server® 2003 do not

restart

Symptom: Servers running Windows Server 2003 do not restart upon power restoration following a power
fail shutdown.
Possible Cause: This is a known Windows Server 2003 behavior on some servers.

Advertising