Using the redundant configuration – HP Tower Uninterruptible Power System User Manual

Page 16

Advertising
background image

Overview 16

Item

Description

1

UPS with an HP UPS Network Module

2

UPS with an HP UPS Network Module

3

HPPP Client server

4

HPPP Client server

5

Network

6

Remote workstation browsing into the UPS Network Module or HPPP
Client over the network

Green

Power connection

Red

Communication path

Using the redundant configuration

Before using a redundant configuration, verify the following:

HP UPS Network Modules and HPPP Clients are installed.

The two UPSs are the same model.

The combined load of UPS 1 and UPS 2 does not exceed 50% of the single UPS load rating.

The redundant UPS feature is designed to maintain power to attached Clients in the event of a utility power

fail condition to a single UPS. In the event of a single UPS power failure you might still experience a graceful
shutdown of Clients if one of the following conditions is present with the unaffected UPS:

The unaffected UPSs has a fault condition (Internal Failure, Overload, Communication Failure) or is in
Bypass.

The combined load of UPS 1 and UPS 2 exceeds 100% of a single UPS rated capacity.

Both UPSs have a fault condition (Internal Failure, Overload, Communication Failure) or are in Bypass.