Ax3 alarm type off, Ax2 sample period 10 seconds, Ax2 hysteresis 3 units – Anderson Manufacturing AV-9000 User Manual

Page 125

Advertising
background image

Section 4

Edition 3
Rev G

4-40

17. Press the

to advance to the next parameter, ALARM 2 SAMPLE PERIOD (only seen if Ax2 TYPE is

RATE).

18. Press the

to advance to the next parameter, ALARM 2 HYSTERESIS.

NOTE: If RATE Alarm is selected, Hysteresis equals RATE in units/TIME BASE.

19. Press the to advance to the next parameter, ALARM 3 TYPE.

* When CONTROL LOOP OPEN is selected for ALARM TYPE and NON PID is selected for CONTROL TYPE (CONTROLLERS section of

CONFIGURATION), prompt LOOP ALARM TYPE will be displayed.

Press the

to change, then

to

desired value, then press the

.

Press the

to change, then

to

desired choice, then press the

.

Press the

to change, then

to

desired value, then press the

.

Ax2 SAMPLE PERIOD

10 SECONDS

Selections

1 to 9999 seconds

Ax3 ALARM TYPE

OFF

Selections for recorder only

OFF

PROCESS - HIGH

PROCESS - LOW

RATE - RISING

RATE - FALLING

Additional selections for use

with controller option

BAND - WITHIN

BAND - OUTSIDE

DEVIATION - ABOVE

DEVIATION - BELOW

CONTROL LOOP OPEN*

P

R

O

C

E
S
S

V

A
R

I

A
B

L

E
S

Note: Units correspond
to units configured in
Process Variables.

Ax2 HYSTERESIS

3 units

Selections

±

999999

(decimal position = 0)

±

9.9999

(decimal position = 4)