Site Requirements 149

Inst

alla

tion

*

In-rush current occurs for 10 to 12 milliseconds

HP recommends the use of magnetic-type circuit breakers, which are capable of handling
large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately
for the steady state currents.

*

Data assumes no other devices share the circuit breaker.

Note

Circuit breaker rating must be adequate for the total current drawn by all
devices on all electrical paths that share a circuit breaker.

Table 16

Disk Enclosure Electrical Requirements

Measurement

Value

Voltage
– Range
– Frequency

220-240V 100 - 127V

50-60Hz

Current
– Typical
Maximum Operating
– 100 - 120 V
– 200 - 240 V
– Maximum In-rush

2.9 - 3.2A

2.6 - 3.2A
5.3 - 6.7A
20A

Table 17

Recommended European Circuit Breakers*

Number of
Components

Breaker
Rating

Breaker Type

1 to 3

16 amps

Type C or Type D per IEC 898

or

Type K per IEC 947-2

4

16 amps

Type D per IEC 898

or

Type K per IEC 947-2