Installation and Wiring

7

ViewStat Color Communicating Thermostat

Communication and Equipment Terminal Wiring Definitions

The following table lists the communication and equipment terminal wiring definitions.

Preparing Captive Wires

Follow these steps to connect the wiring into a captive-wire connector:

1.

Strip 1/4 inch off the wire insulation for all four wires.

2.

Tin 2/3 of the exposed wire.

3.

Insert each wire into the appropriate captive-wire connector up to the insulation.

4.

Tighten the captive screws to secure the fit in the connector.

Communication and Equipment Terminal Wiring Definitions

RH

24 VAC in

RC

24 VAC in for AC relays. If a separate 24 VAC is not supplied
to the RC terminal, you should install a jumper from RH to
RC.

C

24 VAC common

G1

Fan on 1. If you are using a single speed fan, you should
connect it to the G1 terminal. On a multi-speed fan, G1 is the
lowest speed.

G2

Fan on 2. On a multi-speed fan, G2 is the medium speed.

G3

Fan on 3. On a multi-speed fan, G3 is the highest speed.

W1

1st stage heat

W2

2nd stage heat

Y1

1st stage compressor

Y2

2nd stage compressor

B

Reversing valve (heat)

O

Reversing valve (cool)

DEH

Dehumidify

HUM

Humidify

S1

External thermistor. The Color ViewStat supports only one
external sensor.

S2

External thermistor. The Color ViewStat supports only one
external sensor.

L1

AxLink PWR

L2

AxLink AxP

L3

AxLink AxM

L4

AxLink GND