Programming

26

ViewStat Color Communicating Thermostat

AxLink Channels (Cont.)

Channel

Type

Function

Description

149

CMD

Decrement Humidify Set
Point

Continue to decrement the humidify set point
while the channel is active, ON, as if the
decrement button were being pushed.

150

CMD

Increment Dehumidify Set
Point

Continue to increment the dehumidify set
point while the channel is active, ON, as if
the increment button were being pushed.

151

CMD

Decrement Dehumidify Set
Point

Continue to decrement the dehumidify set
point while the channel is active, ON, as if
the decrement button were being pushed.

152-208

Not Used

209

CMD

Fan Speed Low

Set the Fan Speed to Low when the channel
is ON.

210

CMD

Fan Speed Medium

Set the Fan Speed to Medium when the
channel is ON.

211

CMD

Fan Speed High

Set the Fan Speed to High when the channel
is ON.

212

CMD/FDBK Lock Out State

Source ? Master: Set the Lock Out Mode

: TStat: FDBK, Lock Out Mode
Changed

Channel ON: Lock Out Mode Enabled,

Channel OFF: Lock Out Mode Disabled.

213

Not Used

214

CMD

Fan State On

Set the Fan state to On while the channel is
ON.

215

CMD

Fan State Auto

Set the Fan state to Auto while the channel
is ON.

216

FDBK

Fan Status

Feedback, Fan Status changed, Fan status
is controlled by the TSTAT.

Channel ON: Fan is On,

Channel OFF: Fan is Off.

217-218

Not Used

219

CMD

HVAC State Auto

Set the HVAC state to auto while the channel
is active, ON.

220

CMD

HVAC State Cool

Set the HVAC state to cool while the channel
is active, ON.

221

CMD

HVAC State Heat

Set the HVAC state to heat while the channel
is active, ON.

222

CMD

HVAC State Off

Set the HVAC state to off while the channel
is active, ON.

223

CMD

HVAC State Emergency
Heat

Set the HVAC state to Emergency Heat
while the channel is active, ON.

224

FDBK

HVAC Cool Status

Feedback, HVAC Cool Status changed

Channel ON: A/C is On,

Channel OFF: A/C is Off.

225

FDBK

HVAC Heat Status

Feedback, HVAC Heat Status changed

Channel ON: Heat is On,

Channel OFF: Heat is Off.

226

Not Used