Operation

12

900-0112-01-00 Rev B

STATUS LEDS

GREEN

¾ Solid: The inverter is ON and providing power. If accompanied by solid yellow LED, unit is selling power to

the utility grid. (See page 24 for a description of the Sell function.)

¾ Flashing: The inverter has been turned ON but is idle. May be accompanied by the yellow LED. If not

accompanied by the yellow LED, the unit is in inverting mode and is idle due to lack of demand. This can be
because the unit is in Search mode. (See page 14 for a description of Search.)

¾ Off: Unit is OFF. It is not waiting to provide power. Any power present is from another source such as the

utility grid or generator. (See Startup on page 9, or the system display manual, to turn the unit ON.) The unit
may also be a slave that is in Power Save mode. If so, the master inverter may still be providing power to the
system. (See page 27 for a description of Power Save.)

YELLOW

¾ Solid: The AC source is connected and providing power. Unit may or may not be charging the batteries,

depending on settings. May be accompanied by green LED.

¾ Flashing: The AC source is present but has not been accepted. If flashing continues, the unit is refusing the

source. This can occur for the following reasons.

∼ The AC source may have quality issues. External diagnosis may be required. (See page 15 for a

description of input criteria. See the system display manual for diagnosis using the meter displays.)

∼ In the system display, the AC Input menu is set to DROP. (See the system display manual for a

description of the AC IN or

AC INPUT hot key.)

∼ In the system display, the High Battery Transfer (HBX) feature or the Grid Use feature intentionally

disconnected the inverter. (See the system display manual for a description of these modes.)

¾ Off: No AC source is detected. If a source is supposed to be present, confirm the voltage between AC HOT IN

and AC NEUTRAL IN terminals.

RED

¾ Solid: ERROR. Unit has shut down due to a critical problem which may be internal or external to the inverter.

This LED is accompanied by an error message in the system display. See page 37 for a description of
error messages.

¾ Flashing: WARNING. Unit has detected a non-critical problem but has not yet shut down. A warning does

not always lead to a shutdown — if it does, it becomes an error. This LED is accompanied by a warning
message in the system display. See page 37 for a description of warning messages.

¾ Off: No problems are detected.

Table 3

Status LED Quick Reference

Color State

Inverter

State

Notes

Solid GREEN

Inverter is ON and providing power.

If accompanied by YELLOW LED, unit is selling.

Flashing GREEN

Inverter is ON but standing by.

Unit may be in Search mode.

GREEN

Off

Inverter is not providing power.

Unit is either OFF or has been replaced by an
AC source (see next item).

Solid YELLOW

AC source connected and providing
power.

Unit may or may not be charging batteries,
depending on settings.

Flashing YELLOW

AC source present but not yet accepted. Unit may be programmed not to accept the

source, or the source may have quality issues.

YELLOW

Off

No AC source is detected.

If source is present, check AC input.

Solid RED

ERROR. Unit has shut down. See
Troubleshooting.

To see error messages, see the system display
manual.

Flashing RED

WARNING. Unit detected a problem but
has not yet shut down. See
Troubleshooting.

To see warning messages, see the system
display manual.

RED

Off

No problems detected.