Specifications, Table 18 24-volt inverter settings (mate) – Outback Power Systems GFX International Series Operators Manual User Manual

Page 50

Advertising
background image

Specifications

48

900-0112-01-00 Rev B

Table 18

24-Volt Inverter Settings (MATE)

Field Item Default

Minimum

Maximum

search sensitivity (see page 14 for increments)

6 0 50

search pulse length

8 4 20

Search

search pulse spacing

60 AC cycles

4 AC cycles

120 AC cycles

ac transfer control

Grid

Grid or Gen

ac1/grid limit

25 Aac

2.5 Aac

30 Aac

Input

ac2/gen limit

25 Aac

2.5 Aac

30 Aac

low battery cut-out (LBCO)

21 Vdc

18 Vdc

24 Vdc

low battery cut-in (LBCI)

25 Vdc

20 Vdc

28 Vdc

Inverter

adjust output voltage

230 Vac

210 Vac

250 Vac

charger limit

5.5 Aac

0 Aac

6 Aac

absorb voltage

28.8 Vdc

26 Vdc

32 Vdc

absorb time limit

1.0 hours

0.0 hours

24.0 hours

float voltage

27.2 Vdc

24 Vdc

30 Vdc

float time period

1.0 hours

0.0 hours

24.0 hours

refloat voltage

25 Vdc

24 Vdc

26 Vdc

equalization voltage

29.2 Vdc

28 Vdc

34 Vdc

Charger



equalization time period

1.0 hours

0.0 hours

24.0 hours

ac1/grid lower limit

208 Vac

140 Vac

220 Vac

ac1/grid upper limit

252 Vac

250 Vac

280 Vac

ac1/grid input limit

25 Aac

2.5 Aac

30 Aac

Grid

ac1/grid transfer delay

6 AC cycles

0 AC cycles

240 AC cycles

gen input connect delay

0.5 minutes

0.2 minutes

15 minutes

ac2/gen lower limit

208 Vac

140 Vac

220 Vac

ac2/genupper limit

252 Vac

250 Vac

280 Vac

ac2/gen input limit

25 Aac

2.5 Aac

30 Aac

ac2/gen transfer delay

6 AC cycles

0 AC cycles

240 AC cycles

Generator
(Gen)

ac2/gen support

ON

ON or OFF

aux output control

AUTO

ON, OFF, or AUTO

aux output function

Cool Fan

Cool Fan, DivertDC, DivertAC, AC Drop, Vent

Fan, Fault, GenAlert, LoadShed, or Remote

genalert on voltage

22 Vdc

20 Vdc

28 Vdc

genalert on delay

4 minutes

0 minutes

240 minutes

genalert off set point

28 Vdc

24 Vdc

36 Vdc

genalert off delay

9 minutes

0 minutes

240 minutes

load shed off voltage

22 Vdc

20 Vdc

28 Vdc

vent fan on set point

26 Vdc

20 Vdc

32 Vdc

vent fan off period

5 minutes

0 minutes

30 minutes

diversion on voltage

29.2 Vdc

24 Vdc

32 Vdc

Auxiliary
(AUX)

diversion off delay

30 seconds

0 seconds

240 seconds

Stacking

stack phase

Master

Master, OB Slave L1, 3p Classic B, 3p Classic C

master adjust only

0 0 7

Power
Save

slave adjust only

1 1 15

sell re volts

26 Vdc

20 Vdc

30 Vdc

grid tie window

User

IEEE or User

Sell

grid tie authority

GridTie

GridTie or NoSell

vac input adjustment

3

236 220 254

vac output adjustment

3

236 220 254

Calibration
(Cal)

battery vdc adjustment

4

2 0 4

3

These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower voltages. One count equals approximately
1 Vac. The range of adjustment is 15 Vac above nominal and 17 Vac below nominal.

4

These values are in digital counts, not volts. One count equals 0.2 Vdc. The range of adjustment is 0.4 Vdc above or below nominal.

Advertising