Configuration wizard, Figure 164 modifying an existing configuration – Outback Power Systems MATE3 Owners Manual User Manual

Page 135

Advertising
background image

Configuration Wizard

900-0117-01-00 Rev C

133

Figure 164 Modifying an Existing Configuration

Soft Keys:

<Back> moves back one screen.

<Continue> moves forward to the next screen.

Set Points:

System Type (see page 74):

System Type
System Voltage
Array Wattage
Battery Type/Capacity

Battery Charging (see pages 89 and 89):

Absorb Voltage/Time
Float Voltage/Time
Equalize Voltage/Time
Re-Float Voltage

AC Configuration (See pages 83 - 87, and 100):

AC Output Voltage (Vac)
AC Phase
AC Input Breaker Size (amps)
Maximum Output Load (amps)

Generator Configuration (See pages 74 and 115):

Generator Installed – Y or N
Generator TypeAC or DC
Size0.0 to 150.0
Generator Start (manual, auto)
Aux Output Device Port – 1
Control (Radian only; AUX Relay or AUX Output)

Continued on next page...

To modify an existing configuration:

1. Access

the

Main Menu as shown in Figure 71.

2. Select

the

Configuration Wizard menu.

3. Select

Existing Configuration.

4. Select

<Continue>. This will bring up the four

Configuration Wizard programming screens.

5.

Use the control wheel to adjust the settings in each
screen where required. Record the settings on the
form provided in Table 11.