Programming

88

900-0117-01-00 Rev C

AC Output

This menu adjusts the output voltage produced while the inverter is inverting (running on battery power).
This setting does not affect the output when using another AC input source. It does not affect the
acceptance parameters for an AC input source. The range of adjustability will vary with inverter model.
See the inverter Operator’s Manual for the specific range of adjustability.

Figure 96

AC Output

Low Battery

While inverting, the inverter will not be able to sustain its operation if the battery voltage goes below a certain point.
The inverter will stop functioning and generate an error. This function is referred to as a Low Battery Cut-Out (LBCO).
The function is intended to protect the batteries, as excessive discharge may damage a battery. It also protects the
inverter’s output and loads. Continuing to invert on a low DC voltage may produce a distorted waveform.

When this occurs, the Events LED will illuminate to indicate an event has occurred. (See Figure 159 on page 151 for
reviewing event details.)

The range of adjustability for this set point will vary with inverter model. See the inverter Operator’s Manual for the
specific range of adjustability.

The inverter will also stop functioning and give an error due to high battery voltage. However, the high-battery
cut-out voltage is not adjustable.

Figure 97

Low Battery

Set Points:

Output Voltage – Adjusts the inverter’s output voltage

while in inverting mode.

AC Coupled Mode (Radian-class only) – This is a function

which has been included in Radian inverters, but which has
not yet been enabled.

AC Output Screen (FX-class)

AC Output Screen (Radian-class)

Set Points:

Cut-Out Voltage – Sets the voltage at which the inverter

shuts off due to a low-battery condition. If the batteries drop
to this voltage for five consecutive minutes, the inverter will
stop functioning. The inverter’s ERROR LED will illuminate.
The MATE3 will display an event, with a

Low Battery V error

appearing in the

Inverter Errors menu.

Cut-In Voltage – Sets the voltage at which the inverter

recovers from LBCO. If the batteries rise to this voltage for ten
consecutive minutes (usually through charging), the inverter
will begin functioning again. The

Low Battery V error will

clear itself.