Pv200, Closed loop proportional valve controller – High Country Tek ProValve 200 Series User Manual

Page 12

Advertising
background image

021-PV200 Rev A

PV200 Uses Manual

12

Copyright © High Country Tek, Inc.

– 2013

PV200

Closed Loop Proportional Valve Controller

B MAXIMUM OUTPUT - Sets the maximum output current for coil B (Amps). The value in the brackets is the

present output current.

B OVERRIDE -

Sets the output current for a digital reverse override command. No ramping takes place during

override operations. The value in the brackets is the present output current.

DITHER FREQ. - Set the PWM or dither frequency according to the valve specifications. This parameter is variable.

Options: 35, 41, 49, 61, 81, 122, 244, (Select OFF for 15.63KHz)

OUTPUT CURRENT - Displays the present output current. This parameter is a monitor type.

SUPPLY VOLTAGE - Displays the

module’s power supply voltage. It is helpful for troubleshooting. This parameter

is a monitor type.

FAULT STATUS - The Fault LED displays solid red light for both coil open and short until cycling the power to clear

the fault. Moving command signal out of active range will not clear faults.