Pv200, Closed loop proportional valve controller – High Country Tek ProValve 200 Series User Manual

Page 16

Advertising
background image

021-PV200 Rev A

PV200 Uses Manual

16

Copyright © High Country Tek, Inc.

– 2013

PV200

Closed Loop Proportional Valve Controller

Switch the

“reverse override” OFF and switch the

“forward override” ON. The PV200 becomes an
open loop controller. Coil A current is set to the
override current setting of 0.5A.

The

Reverse

override has a higher priority than the

forward override.

By switching OFF both override inputs, the PV200
resumes normal closed-loop operation and coil B
current is 0.68A because the actual position 0% is
less than the target position 56%.