2.2 Specifications

The various specifications of the UPS system are provided in the following tables.

Table 4: ELECTRICAL SPECIFICATIONS

Electrical Specifications

Input Specification

Nominal Input Voltage

120 VAC, Single Phase

Input Voltage Range

85 VAC to 135 VAC

Input Frequency

45 to 65 Hz (+/- 5%)

Input Configuration

3 Wire (Hot, Neutral & Ground)

Input Current (Max. draw)

8.8 amps, Power-Factor Corrected

Input Protection

Input breaker 15 amps (20 amps PD1250 (PLUS) &

SP2000)

Output Specification

Nominal Output Voltage

120 VAC, Single Phase

Power Rating

1.25 KVA (1250VA/875W), 2KVA (2000VA/1400W)

Output Voltage Regulation

+/- 2% for 100% step load change and from

High battery to Low battery condition

Output Frequency

50 or 60 Hz (+/- .5%) unit not in sync.

Output Configuration

3 Wire (Hot, Neutral & Ground)

Output Wave Form

True Sine wave

Overload capability

110% for 10 minutes 200% for 50 milliseconds

2k PLUS 160% for 10 seconds

Fault clearing

Current limit and automatic shutdown

Short circuit protection

Current limit and automatic shutdown

Efficiency

90% at full load (on utility)

Load Power Factor

.7 lagging through unity to .7 leading