Table 9: clary outposttm batteries – Clary SP Series-Model PD User Manual

Page 19

Advertising
background image

T H E C O N T I N U O U S P O W E R C O M P A N Y

19

Table 9: CLARY OutPost

TM

BATTERIES*

Estimated Runtime

(Per set @ 77°F / 25°C)

(New Batteries, fully

charged)

Unit

Weight

Overall Dimensions

Per Battery Inches (cm.)

Clary

Part. No.*

Volts/

A-hrs.

300

Watts

500

Watts

700

Watts

875

Watts

Lbs.

(Kg.)

Length

L

Width

W

Height

H

OP72C

(Set of

Six

Batteries)

12

VDC/

41 AH

6.5

Hrs.**

4.0

Hrs.**

2.5

Hrs.**

1.8

Hrs.**

29

(13.2)

7.68

(19.6)

5.15

(13.1)

7.9

(20.1)

*OP72X battery sets include six (6) batteries per set. Wired in series, each set provides 72 VDC.

** Actual times may vary, runtimes are dependent on many factors.

Lower/Higher AH capacity batteries, allowing less or more runtime, are available on special order.

Contact factory for more information.

Communications, Controls & Diagnostics

Alarm Function Monitoring: The traffic UPS comes standard with a DB-9F connector with open

collectors (40 V @ 20 mA) indicating On-Battery, Low-Battery, Timeout on-battery and Alarm.

A separate RS232 Interface is provided via a DB-9F connector allowing full, interactive, remote

computer monitoring and control of the UPS functions via standard UPS protocols.

Optional TCPIP/Ethernet available, contact factory for more information.

Front Panel controls: Power ON, Cold (DC) Start, Alarm Silence, Battery Test, Bypass Circuit

Breaker, and DC/Battery Circuit Breaker.

Options

Battery Tray to hold three (3) OP72C batteries is 19” wide for use in 170 type cabinets and

mounts on standard RETMA rails.

Swing-out Battery Box, mounts on right rail inside back door of 170 type cabinets. Box is designed

to hold tree (3) OP72C batteries

Fast Battery Module, optional module provides extra charging current to the batteries when

required, reducing charging time.