104

FlowTbl[8].FlowPFS

float

Flow Linearizer Index 8 PFS [0.0 – 1.0]

105

FlowTbl[8].LinCounts

uint

Flow Linearizer Index 8 Counts

106

FlowTbl[9].FlowPFS

float

Flow Linearizer Index 9 PFS [0.0 – 1.0]

107

FlowTbl[9].LinCounts

uint

Flow Linearizer Index 9 Counts

108

FlowTbl[10].FlowPFS

float

Flow Linearizer Index 10 PFS [0.0 – 1.0]

109

FlowTbl[10].LinCounts

uint

Flow Linearizer Index 10 Counts

110

PulseMeasInt

uint

Flow Pulse Measure Interval in mS [500-60000]

111

FlowMeasureMode

uint

Flow measure mode [0-4]

112

Flow_NRF_NSample

uint

Flow NRF Number of Samples [1-32] for PWM

113

Flow_NRF_ErrLimit

float

Flow NRF Error Value [0.05 10.0]%F.S. for PWM

114

Flow_NRF_TimeLimit

uint

Flow NRF Time Interval for PWM [0-199], 0-dis'd

115

Flow_Damping

uint

Reading Damping 1-99 (sec.) for PC mode

116

Flow_Window

uint

Flow running average window for PC mode [0-100], 0-dis'd

117

FlowAWD_NRF_NSample

uint

Flow NRF Number of Samples [1-32] for AWD

118

FlowAWD_NRF_ErrLimit

float

Flow NRF Error Value [0.05 10.0]%F.S. for AWD

119

FlowAWD_NRF_TimeLimit

uint

Flow NRF Time Interval for AWD [0-199], 0-dis'd

120

Min_Freq_PWM

uint

Minimum measure Frequency for PWM model

121

Max_Freq_PWM

uint

Maximum measure Frequency for PWM model

122

Min_Freq_AWD

uint

Minimum measure Frequency for AWD model

123

Max_Freq_AWD

uint

Maximum measure Frequency for AWD mode

124

AWD_DC_Offset

uint

AWD DC offset for AWD mode (def. 2225 counts)

125

AWD_Tresh_PFS

uint

AWD threshold in % of Average DC offset for AWD mode (1 - 80)

126

FFT_DSP_Enable

uint

FFT algorithm Enable/Disable

127

FFT_Sample_Rate

uint

FFT Sample Frequency: 0-Auto,1 - 8000, 2 - 4000, 3 - 2000,
4 - 1000, 5 - 500Hz

128

FFT_Triger_Level

uint

FFT Trigger level counts (0-4095)

129

FFT_NoiseTreshold

float

FFT Noise threshold counts (0-4000)

130

DP_Channel_1

uint

Sensor#1 DP master attenuator setting (original)

131

DP_Channel_2

uint

Sensor#2 DP master attenuator setting (original)

132

Auto_Att_Mode

uint

Signal Auto Attenuation Mode: 0-Dis'd, 1-Enb'd

133

Auto_Att_Target_Level

float

Signal Auto Attenuation Target level (RMS counts)

134

Meter_Pipe_ID

float

Meter or Pipe Internal Diameter (inch)

135

Meter_FS_Range

float

Meter Full Scale range in L/min

136

MeterCalFactor

float

Calibration Factor:[Hz/l/min] (for STD conditions)

137

Vortex_Coeff_Ck

float

Manuf. Specific settings (do not change)

138

LowFlowCutOff

float

Meter low flow cut off [0 - 25.0 %F.S.]

139

Low_Freq_CutOff

float

Meter Low Frequency cut off (Hz)

140

High_Freq_CutOff

float

Meter High Frequency cut off (Hz)

Advertising