2dimensions and installation – Horner APG SmartBlock HE-579ACM300 User Manual

Page 2

Advertising
background image

PAGE 2

12 May 2011

MAN0951-02

HE-559ACM300

Information is subject to change without notice.

2

DIMENSIONS AND INSTALLATION




Network, Power and Grounding:
A single 5 pin connector is used to make both a network connection and power input. A quality class 2
power supply should be used for this product. If the power is run with the network cable, care must be
taken such that the voltage does not drop below the lower supply limit on longer runs.

A quality protective earth ground is required for safe and proper operation. The best protective earth
ground is achieved by screwing the lower left grounding location into a grounded back plate. Alternately
a protective earth ground can be connected to the spade lug.

Please see Horner manual MAN0799 for details on CAN wiring.

CAN Network & Power Port Pin Assignments

Pin

Signal

Signal Description

Direction

1

V-

CAN and Device

Ground - Black

!

2

CN_L

CAN Data Low - Blue

In/Out

3

SHLD

Shield Ground - None

!

4

CN_H

CAN Data High - White

In/Out

5

V+

Positive DC Voltage

Input (10-30VDC) - Red

!

4.56”
(115.8mm)

4.48”
(113.7mm)

2.16”

(54.8mm)

With connector

2.84”

(72.1mm)

CAN Network & Power

Connector

Torque rating 4.5 – 7 Lb-In

(0.50 – 0.78 N-m)


J1
CTs and Relay

J2
Voltage Inputs

Can and
Power
Connector

Network ID
Selector
Switches

Status LEDs

Earth Ground
Location