NETWORK DATA

Consumed Digital Data – This data is sent from the controller to the SmartBlock. For typical
applications the I/O configuration setup in Cscape will automatically populate this data.
For more
advanced applications you may use NetPut functions to write this data. Please see the advanced
programming guide MAN0880 for more details.

Bit

Description

1

Q1 default

2

Q1 override
Upon module stop / timeout, if Q1 override is true, Q1 is set to Q1 default, otherwise the Q1
value is held. This override / hold polarity is consistent with OCS / Cscape usage but the
reverse of the legacy analog hold / override polarity in word 5.

3

Frequency Source, Set for phase B, Clear for phase A or C

4

Frequency Source, Set for phase C, Clear for phase A or B
If Clear Always accumulate Watt-Hours

5

If Set

Do not accumulate Watt-Hours if load is under 0.005% of full scale to avoid meter
creep due to slight zero errors

6

Set to report period instead of frequency in AI13 / AI14

17

Relay output, set to ON to close N.O. and open N.C contacts.

23

Set to ON to clear KWhr, set to OFF to re-enable KWhr accumulator

24

Set to ON to clear Status flags, set to OFF to re-enable Status flags

Produced Digital Data – This data is sent from the SmartBlock to the controller. Normally this data is
mapped into specific registers in the I/O configuration in Cscape.
For advanced applications NetGet
functions can be used to obtain this data. Since this data is broadcast to all controllers on the network
additional controllers can use NetGet functions to obtain this data as well.

Bit

Name

Description

I1

AEHF

Watt-Hour accumulator half full.

I2

REHF

VAR-Hour accumulator half full

I3

VAEHF

VA-Hour accumulator half

I4

SAGA

Voltage sag on Phase A

I5

SAGB

Voltage sag on Phase B

I6

SAGC

Voltage sag on Phase C

I7

ZXTOA

Zero Cross timeout on Phase A

I8

ZXTOB

Zero Cross timeout on Phase B

I9

ZXTOC

Zero Cross timeout on Phase C

I10

ZXA

Zero Cross detected on Phase A

I11

ZXB

Zero Cross detected on Phase B

I12

ZXC

Zero Cross detected on Phase C

I13

LENERGY

Reserved

I14

RESET

5V supply rail under 4 volts

I15

PKV

Peak voltage level exceeded

I16

PKI

Peak current level exceeded

I17

WFSM

Reserved

I18

REVPAP

Sign changed occurred in Watt calculation

I19

REVPRP

Sign changed occurred in VAR calculation

I20

SEQERR

A-B-C Rotation