Fig.4

2300

600

Soot Door

Appliance

FLUE PIPES

A flue pipe should only be used to connect an appli-
ance to a chimney and should not pass through any
roof space.

Flue pipes may be of any of the following materials:

(a) Cast iron as described in BS 41: 1973 (1981),

or

(b) Mild steel with a wall thickness of at least 3mm,

or

(c) Stainless steel with a wall thickness of at least

1mm and as described in BS EN 10095:
1999 Specification for stainless and
heat resisting steel plate, sheet and strip, for
Grade 316 S11, 316 S13, 316 S16, 316 S31,
316 S33, or the equivalent Euronorm 88-71
designation, or

(d) Vitreous enamelled steel complying with BS

6999: 1989.

Flue pipes with spigot and socket joints should be
fitted with the socket uppermost.

CHIMNEY

The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.
The chimney must have a cross sectional area of at
least 19350 square mm (30 square inches) or a
diameter of 150mm (6 “). The chimney should be
checked for soundness and draught before installa-
tion. The stove must be connected to a chimney

with a minimum continuous draught of 15 Pascals.
Poor draught will result in poor performance.
Similarly an excessive draught will result in the appli-
ance over firing or being difficult to control. An
excessive draught may require a flue draught sta-
biliser to be fitted. Do not connect this appliance to a
chimney serving another appliance. The minimum
required chimney height is 4.5 metres from the floor
on which the appliance is installed. An existing
masonry chimney should be inspected and if neces-
sary, repaired by a competent mason.

DOWN DRAUGHTS

However well designed constructed and positioned,
the satisfactory performance of the flue can be
adversely affected by down draught caused by near-
by hills, adjacent tall buildings or trees. These can
deflect wind to blow directly down the flue or create
a zone of low pressure over the terminal. A suitable
anti-down draught terminal or cowl will usually effec-
tively combat direct down blow but no cowl is likely
to prevent down draught due to a low pressure zone.

VENTILATION & COMBUSTION AIR
REQUIREMENTS

This appliance is rated at no more than 8kW. It is
imperative that there is sufficient air supply to the
stove in
order to support correct combustion. The air supply
to this appliance must comply with B.S. 8303: Part 1
and current Building Regulations. The minimum
effective air requirement for this appliance is
16.5cm

2

.

If a draught stabiliser is used then this increases to
40.5cm

2

. When calculating combustion air require-

ment for this appliance use the following equation: a
total free area of at least 550mm

2

per kW of rated

output above 5kW shall be provided. If there is
another air using appliance fitted in the same or
adjacent room, it will be necessary to calculate addi-
tional air supply. All materials used in the manufac-
ture of air vents should be such that the vent is
dimensionally stable and corrosion resistant.

The effective free area of any vent should be ascer-
tained before installation. The effect of any screen
should be allowed for when determining the effective
free area of any vent.

Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.
An air vent outside the building should not be locat-
ed less than the dimensions specified within the
Building Regulations from any part of any flue termi-
nal.