SECTION 1. FUNCTIONAL MODES

1-7

TABLE 1.7-1. *C Mode Entries and Codes

Key

Display

Entry

ID: Data

Description

*C

12:0000

Enter current password.
If correct, then advance,
else exit *C Mode. 12:00
indicates *C Mode is not
in PROMs. If security is
disabled, *C advances
directly to window 1.

A

01:00

Window 1, enter
command:
00 = disable security and

advance to window
2; subsequent *0 or
*6 enables security.

01 = security remains

enabled, but it
advances to window
2 and allows entry of
a new password.

A

02:XXXX

Set new password
(XXXX is current
password).

A

Returns to window 1.
Entering 0000 disables
security (window 1 must
be set to 0).

1.8 *D MODE -- SAVE OR LOAD

PROGRAM

The *D Mode allows the user's program
information in the *1, *2, *3, *4, *A, *C (if OSX-
0), and *B Modes to be output to or loaded from
printer/computer (ASCII) or SM192/716 Storage
Module. Table execution and on-line printer
outputs are suspended while in the *D Mode.
When *D is keyed, the CR7 will display "13:00".

TABLE 1.8-1. *D Mode Commands

Command

Description

1

Save ASCII Program

2

Load ASCII Program

71

Save/Load/Clear Program
from Storage Module

A command is entered by keying the command
number and A. When Command 1, 2, or 71 is
entered, the command number is displayed in
the ID field. The user must then key in a baud
rate code for command 1 or 2 or the command
code for the Storage Module (Table 1.8-2).
After the code is keyed in, key A to execute the
command. After a command is executed,
"13:0000" is displayed; *D must be entered
again before another command can be given.

If the CR7 program has not been compiled
when a command to save the program is
entered, it will be compiled before the command
is executed.

TABLE 1.8-2. *D Mode Baud Rate and

Storage Module Codes

BAUD RATE

STORAGE MODULE

CODES

COMMAND CODES

0 - 300 baud

1X Save Program X to

1 - 1200

Storage Module

2 - 9600

(X=1-8)

3 - 76,800

2X Load Program X from

Storage Module
(X=1-8)

3X Erase Program X from

Storage Module
(X=1-8)