SECTION 1. FUNCTIONAL MODES

1-9

LOAD PROGRAM FROM ASCII FILE

Command 2 sets up the CR7 to load a serial
ASCII program. The format is the same as sent
in response to command 1 (Table 1.8.4).
Except when in telecommunications, the baud
rate code must be entered after command 2.

A download file need not follow exactly the
same format that is used when listing a program
(i.e., some of the characters sent in the listing
are not really used when a program is loaded).
Some rules which must be followed are:

1.

"M" must be the first character other than a
carriage return (CR) or line feed (LF). The
"M" serves the same function as "*" does
from the keyboard. The order that the
Modes are sent in does not matter (i.e., the
information for Mode 4 could be sent before
that for Mode 1).

2.

"S" is necessary prior to the execution
interval (Scan rate).

3.

The colons (:) are used to mark the start of
actual data.

4.

A semicolon (;) tells the CR7 to ignore the
rest of the line and can be used after an
entry so that a comment can be added.

There are 4 two-character control codes which
may be used to verify that the CR7 receives a
file correctly:

^B ^B

(2hex, 2hex) Discard current buffer

and reset signature

^C ^C

(3hex, 3hex) Send signature for

current buffer

^D ^D

(4hex, 4hex) Load current buffer and

reset signature

^E ^E

(5hex, 5hex) Exit and compile program

As a download file is received, the CR7 buffers
the data in memory; the data is not loaded into
the editor or compiled until the CR7 receives a
command to do so. The minimum file that
could be sent is the program listing, then ^E^E.
^C^C tells the CR7 to send the signature
(Section C.3) for the current buffer of data. If
this signature does not match that calculated by
the sending device, ^B^B can be sent to
discard the current buffer and reset the
signature. If the signature is correct, ^D^D can
be sent to tell the CR7 to load the buffer into the
editor and reset the signature. Once the
complete file has been sent and verified, send
^E^E to compile the program and exit the load
command.

1.8.2 PROGRAM TRANSFER WITH STORAGE

MODULE

The SM192/716 Storage Module must be
connected to the CR7. Key *D, then enter
command 71. The command to save, load, or
clear a program and the program number
(Table 1.8-2) is entered. After the operation is
finished, "13:0000" is displayed.

The datalogger can be programmed on power-
up using a Storage Module. Storage Modules
can store up to eight separate programs. If a
program is stored as program number 8, and if
the Storage Module is connected to the
datalogger serial port at power-up, program
number 8 is downloaded to the datalogger and
compiled.