4.1.3 Desiccant

Humidity is monitored inside the T107’s enclosure using the Elan HM2000 (pn

10070) RH sensor that is incorporated in the enclosure. Change the desiccant

packs when the enclosure RH exceeds 50%. The enclosure RH sensor should

be changed every 5+ years. The enclosure RH is displayed in Toro T.Weather

software.

Desiccant packs may be ordered in quantity of 20 individually sealed packs at a

time (pn 6714) or by the individual pack (pn 4905). Campbell Scientific does

have a $50.00 minimum charge. Any orders under $50.00 require a $15.00

handling fee. Call Campbell Scientific or your local Toro distributor for pricing.

4.1.4 Sensor Maintenance

Sensor maintenance should be performed at regular intervals, depending on the

desired accuracy and the conditions of use. A suggested maintenance schedule is

outlined below. See Appendix A for an example of a maintenance log file. Log

file is for one year of station use.

1 week

Check the rain gage screen and funnel for debris and level.

1 month

Check the solar radiation sensor (pyranometer) for level and

contamination. Gently clean with blast of dry air, soft camel hair brush, or

clean water if needed.

Handle the pyranometer carefully when cleaning. Be careful

not to scratch the surface of the sensor.

Do a visual/audio inspection of the 034B-ET’s anemometer at low wind

speeds. Worn bearings can cause the wind cups to spin in an uneven

manner and/or make a grinding sound.

Check the WindSonic1-ET for contamination. If needed, gently clean the

WindSonic1 with a cloth and mild detergent.

When cleaning the WindSonic1, do not use solvents and

avoid scratching the sensor.

3 months

Clean the Gill Radiation Shield by removing the two Phillips screws

holding it to the sensor arm. Gently pull the sensor out of the shield. Clean

the gill shield using warm mildly soapy water. Rinse with clean water and

allow the shield to dry before putting it back on the sensor arm.

If necessary clean the white filter element on the end of the temp/RH

sensor. To clean the filter, unscrew it from off the end of the sensor and

put it in a cup of CLEAN DISTILLED WATER. Use no soap. Agitate the

CAUTION

CAUTION