Page 67: No response using the cr1000kd keypad, 1. cr1000 lithium battery specifications

Advertising
background image

T107 Weather Station

Replace the battery when voltage is approximately 2.7 V. If the lithium cell is

removed or allowed to discharge below the safe level, the T107 will still

operate correctly while powered. Without the lithium battery, the clock will

reset and data will be lost when power is removed. Contact your local Toro

distributor.

Toro recommends factory replacement of the lithium

battery. Misuse of the lithium battery or installing it

improperly can cause severe injury. It is a fire, explosion,

and severe burn hazard! Do not recharge, disassemble,

heat above 100°C (212°F), solder directly to the cell,

incinerate, nor expose contents to water. Lithium batteries

need to be disposed of properly.

The lithium battery contained inside of the T107’s canister is pn 13519.

TABLE 4-1 lists the specifications of the battery.

TABLE 4-1. CR1000 Lithium Battery Specifications

Manufacturer

Tadiran

Model

TL-59025 (3.6 V)

Capacity

1.2 Ah

Self-discharge rate

1%/year @ 20°C

Operating temperature range

-55°C to 85°C

4.2 Troubleshooting

4.2.1 No Response Using the CR1000KD Keypad

Check keypad response after each of the following steps.

A. Make sure the battery has been installed and the PS100 power switch is set

to “ON” (Section 2.8, Battery Installation).

B. Use a voltmeter to measure the voltage on the 12 V and G terminals (see

FIGURE 2-44); the voltage must be between 9.6 and 16 Vdc.

Use a voltmeter to measure the voltage on the 5V and G terminals (see

FIGURE 2-44); the voltage must be between 4.9 – 5.1 Vdc.

C. Disconnect the Temp/RH sensor from the back of the enclosure.

D. Disconnect the 9-pin ribbon cable from any communication option used

with the station so that only the keypad is attached to the 9-pin plug in the

lower right hand corner of the enclosure.

E. Cycle the power to the datalogger by switching the PS100 power supply to

“OFF”, then to “ON” or disconnecting and reconnecting the battery plug.

Keypad should power up and the Campbell Scientific logo and text

appears on the display.