Customer-supplied sensors used with the EVR1500 environmental monitor

appliance must meet the requirements shown in the following table.

Requirements for Customer-Supplied Sensors

Analog Sensors

Requirements

Power

Must accept 12 VDC if powered by EVR1500
environmental monitor appliance.

Input Voltage

Positive voltage between Ø to 40 V;
Example input minimum voltages are 1, 0, 0, 2.
Example input maximum voltages are 5, 5, 10, 10.

Input Current

4-20 mA sensors can be used with an external resistor

or the internal jumpers. Contact Avocent
Technical Support.

Pinout for RJ-45

Pin 1, ground.

Pin 5, voltage input (from sensor to EVR1500
environmental monitor appliance).

Pin 8, - +12 V output (from EVR1500 environmental
monitor appliance to sensor).

Scale

Linear input required.

Digital Sensors

Input Voltage

Ø to 5 VDC.

Pinout

See Appendix C.