ViewStat Installation and Wiring

14

ViewStat Communicating Thermostat

Connecting to an Axcess Control System (via AXC-232++, AXB-EM232,
or Axcent3/PRO)

To connect the ViewStat to an Axcess control system via an Axcess Cardframe (cardframe must be equipped
with an AXC-232 232/422/485 Control Card), AXB-EM232 Enhanced Master, or Axcent3(PRO) Controller,
refer to the card-edge pinout information below:

FIG. 8 shows the wiring configuration for Axcess systems:

It is important that the correct pairing is observed. Transmit, Receive, and Mic
need to be on twisted pairs. Splitting pairs (e.g., using a white/green wire with a blue/
white wire for transmit) will result in increased crosstalk, and may result in bus failure
or noise on the intercom.

Axcess System Card Edge Pinouts

Pin

Signal

Function

1

GND

Ground (RS-232)

2

RX

Receive data (RS-232)

3

TX

Transmit data (RS-232)

4

+12V

Power

5

RX -

Receive data (RS-422)

6

RX +

Receive data (RS-422)

7

TX -

Transmit data (RS-422)

8

TX +

Transmit data (RS-422)

9

GND

Ground

10

CTS

Clear-to-send (hardware handshaking)

11

RTS

Ready-to-send (hardware handshaking)

12-16

not used

FIG. 8

Connecting the ViewStat to an Axcess Control System

ViewStat
(Communication
terminal)

Axcess
Control
System

AXC-232(++)
or
AXB-232(++)