VENTILATION / FAN CYCLING SETTINGS

The Aprilaire Dehumidifier has the option
to monitor HVAC heating, cooling and fan
calls to assure the HVAC fan has
operated a predetermined amount of
time each 1/2, 1, 2 or 3 hours. The
dehumidifier can also open a normally
closed damper in an outdoor air intake to
ventilate during this predetermined
amount of time. This feature will
function even if the dehumidifier is
turned off at the dehumidifier or Model
70 Living Space Control. The only way to
disable this feature is by turning the
Cycle Time setting to OFF or turning
power off at the On/Off switch.

HVAC EQUIPMENT

THERMOSTAT

WIRE NUT

DEHUMIDIFIER

CONTROL

24 VAC

(10 VA min)

TRANSFORMER

DAMPER

VENTILATION

OPTIONAL

G

R

C

G

W

Y

Y

W

C

R

A+

B

DEH

REMOTE

HV
AC EQUIP

.

VENT

Cf

Gs

Gh

W

-

Y

Rf

DAMPERS

OPTIONAL OUTDOOR

TEMPERATURE SENSOR

(Model 8052)

SENSOR

ODT

SWITCH

FLOA

T

FIGURE 12

90-968

First, set the 1/2, 1, 2 or 3 hour period by setting the CYCLE PERIOD dip switches to determine
how often the dehumidifier should look to ventilate or cycle the HVAC fan.

Next, use the CYCLE TIME dial to determine how long during every cycle period the HVAC fan
should operate. Adjust the dial from OFF to between 1 to 60 minutes. This will give you HVAC fan
operation from 1 to 60 minutes every 1/2, 1, 2 or 3 hours. A call for heat, cooling or fan from the
HVAC equipment will often satisfy the run time requirement. If not, the dehumidifier will turn on
the HVAC fan to assure that the cycle time is met. For example: If the home requires
ventilation of 20 minutes every two hours set the CYCLE PERIOD Dip Switch for 2 hours
to ON and rotate the CYCLE TIME to 20 minutes. If the HVAC equipment only has to run
for 10 minutes, the dehumidifier will turn on the HVAC fan for 10 minutes at the end of
the 2 hours to assure the ventilation / fan cycling time.

Finally, if using the Ventilation Damper, determine if the ventilation should be restricted based
on outdoor temperature. Set the VENT-AUTO / VENT-TIMED dip switch to VENT-AUTO
(see Figure 15) to prevent opening the ventilation damper if the outdoor air is above 100°F,
below 0°F or except with a heat call between 20°F and 0°F. In the VENT-TIMED setting the
ventilation damper is activated regardless of outdoor conditions. Note: The Outdoor
Temperature Sensor (Model 8052) must be installed for this to work.

You can also check the wiring of the dehumidifier to the HVAC equipment. If you rotate the
CYCLE TIME dial to TEST, the HVAC fan should come on and the Ventilation Damper
(if equipped) should open. DO NOT leave the CYCLE TIME in TEST.

FIGURE 14

90-783C

FIGURE 13

ON

1234

2 HOUR
3 HOUR

30 MIN.
1 HOUR

CYCLE PERIOD

90-783C

CYCLE TIME

TEST

60

MIN.

OFF

0

MIN

MIN.

30

MIN.

(shown set
to 1 hour)

FIGURE 15

4

3

2

1

ON

VENT-TIMED

HVAC FAN

SYSTEM SETUP

ON

MODEL 70

CONVERTIBLE

HVAC FAN

WHL HOUSE

VENT-AUTO

MODEL 70

OFF

90-969

(shown set to
30 minutes)