Ventilation / fan cycling settings – Aprilaire 1700 User Manual

Page 11

Advertising
background image

11

VENTILATION / FAN CYCLING SETTINGS

(CONTINUED)

• An Aprilaire

®

Normally-Closed Damper (Model 6506) should

be installed in the outside air intake. It should be wired to the
terminals labeled “VENT DAMPER” on the dehumidifier
control board. Follow all installation instructions supplied
with the damper. Refer to each installation for ducting.

• The Outdoor Temperature Sensor (Model 4278) should be

installed outside in a shaded location (Figure 16) or in an
outside air intake duct, but no more than 3 feet from the
outside (Figure 17).

• The Outdoor Temperature Sensor is not affected by wire

length. However, do not route the wire alongside wires
carrying high voltage (115 VAC or greater), as interference
may occur.

• Connect the wires from the sensor to the terminals labeled “ODT SENSOR” on the dehumidifier.

See Figure 12 for terminal locations.

This installed option allows outside air to be combined with
the fan cycling feature from the dehumidifier, provided the
outside air temperature is in the acceptable range (0-100°F).
Note: The dehumidifier can control the HVAC fan to provide
fan cycling, regardless of whether or not an outdoor
ventilation duct is installed.

NORTH, EAST
OR WEST SIDE
OF HOME

OUTDOOR

TEMPERATURE

SENSOR

SENSOR

SENSOR
BRACKET

ABOVE EXPECTED

SNOW LINE

OUTDOOR

TEMPERATURE SENSOR

LEADS

36" MAX.

CENTER LINE

OUTSIDE WALL

B2202617-D

B2202617-E

FIGURE 16

FIGURE 17

House Size

Bedrooms

(square feet)

2

3

4

5

1000-1500

20

25

30

35

1501-2000

25

30

30

35

2001-2500

25

30

35

40

2501-3000

30

35

40

40

3001-3500

30

35

40

45

TABLE 1 – Air Cycling Time Setting (min./hr.)

VENTILATION GUIDELINES

1. Based on ASHRAE 62.2 ventilation

requirement.

2. Based on outside air duct of 6”

dia., 20’ long flex duct, 0.15” w.c.
static pressure at outdoor air duct.

3. Based on ‘Cycle Period’ being in

the default (1 hour) position.

4. A longer outside air duct and/or

lower static pressure will require a
longer Ventilation Time.

As an example, for a 2,500 square foot home with 3 bedrooms, set the cycle time to 30 minutes of ventilation per one-hour cycle.

A longer outdoor air intake duct or lower return static pressure will increase the ventilation time required. Additionally, local
codes may affect the setting.

Advertising