Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

31

Operation Modes

On-line Operation

During on-line operation, the critical load is supported by the inverters. The main inverter controls
the output voltage and the delta inverter controls the input current. The delta inverter also provides
battery-charging current. While the UPS is running in this mode, a single-line diagram will appear on
the screen. The green line indicates the power flow from the utility supply through the UPS to the
load.

CAUTION!
Do not open Q2 when the UPS is in on-line operation, as this action may result in a load
drop or a failure of the UPS to support the load.

Breaker Identification

Q1

UPS input breaker

Q5

Static bypass input breaker

Q2

UPS output breaker

Q7

Battery breaker 1

Q3

Manual bypass breaker

Q8

Battery breaker 2

Note

Only operate a breaker when the associated breaker lamp is on.