37

System Shutdown from Online to Manual
Bypass Operation

To shut down the UPS (transfer from on-line operation to manual bypass operation), follow the
screen-prompted instructions as illustrated.

CAUTION!
Do not open Q3 when the UPS is in manual bypass operation, as this action may result in
a load drop or a failure of the UPS to support the load.

Normal

Normal

UPS Shutdown

5.40 PM

Initiate transfer to static bypass

Close breaker Q3

Open breaker Q5

Push UPS "OFF" button

Open breaker Q2

Open battery breakers Q7 and Q8

Open breaker Q1

Initiate transfer

Load will be on manual bypass

SSW input

UPS power down

UPS output

Isolate UPS from battery

UPS input

Normal

~

~

Q7

Q8

Normal

0:00 AM

Q2

UPS Summary

Normal

5.40 PM

Startup

Shutdown

Network Configuration

User Configuration

View Event Log

Predictive Maintenance

Static Bypass Online

Online Static Bypass

Transfer from manual bypass to online

Transfer from online to manual bypass

Transfer from online to static bypass

Transfer from static bypass to online

Operation

Normal

Select Operation/
Configuration

Select Shutdown

Follow the shut-down
instructions on the screen.

All instructions initially
appear in red. Once a
command has been carried
out successfully, its text will
change to green.