Manual bypass operation – American Power Conversion Bypass Static User Manual

Page 40

Advertising
background image

34

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

Manual Bypass Operation

During manual bypass operation, the critical load is supplied directly by utility power, making it
possible to isolate the UPS and the Bypass Static Switch for maintenance.

A single-line diagram will appear on the screen, with an orange line indicating the power flow from
the utility to the load via the Q3 breaker.

Note

Battery power is not available as an alternate power source while the system is running
in manual bypass operation.

CAUTION!
Do not open Q3 when the UPS is in manual bypass operation, as this action may result in
a load drop or a failure of the UPS to support the load.

Breaker Identification

Q1

UPS input breaker

Q5

Static bypass input breaker

Q2

UPS output breaker

Q7

Battery breaker 1

Q3

Manual bypass breaker

Q8

Battery breaker 2

Note

Only operate a breaker when the associated breaker lamp is on.