Sprinkler Option Temperature Controller Settings

NOTE: Refer to Controller’s User’s Manual for further information on controller options.

Message

Display

Message

Description

Settings

SP

TEMPERATURE

SET POINT

575º F OR 301.6º C

ALHi

ALARM HI

575º F OR 301.6º C

(NOTE: ADJUST SAME AS SP)

InP

INPUT DEVICE

P 385 = RTD

INPUT

F-C

º F OR º C

SELECT TYPE REQUIRED

(FAHRENHEIT OR CELSIUS)

dpt

DECIMAL POINT

0,

N

O DECIMAL POINT

InPt

INPUT FAULT TIMER

0.2

SPL

SET POINT LOW

500

(SETTING CAN NOT BE LOWER)

SPH

SET POINT HIGH

700

(SETTING CAN NOT BE HIGHER)

SPSt

SET POINT STATE

rE

(REVERSE ACTION)

SPOL

SET POINT OUTPUT

LOW LIMIT

0%

(NOT USED)

SPOH

SET POINT OUTPUT

HIGH LIMIT

100%

(NOT USED)

SPLP

SET POINT LAMP

0 OFF

(LAMP OFF WHEN OUTPUT IS ON)

AL

HIGH ALARM ONLY

Hi

ALt

ALARM TYPE

Abs

(ABSOLUTE ALARM)

ALrE

ALARM RESET

OnOf

(AUTOMATIC RESET)

ALPi

ALARM POWER

INTERRUPT

OFF

(ALARM INHIBIT IS OFF)

ALiH

ALARM INHIBIT

OFF

(ALARM INHIBIT IS OFF)

ALSt

ALARM OUTPUT

STATE

CLOS

(CLOSES CONTACTS AT ALARM SET POINT)

ALLp

ALARM LAMP

O ON

(ALARM LAMP IS ON WHEN ALARM

CONTACT IS CLOSED)

SECr

SECURITY CODE

FULL SECURITY -

SET TO 110 (DISPLAYED AS 1) "VIEW ONLY"

NO SECURITY -

SET TO 111 (DISPLAYED AS 4)

"ALL FEATURES UNLOCKED"