Default initialization – Kantech KT-400 User Manual

Page 34

Advertising
background image

DN1726-0811

30

Default initialization

The KT-400 default initialization or Factory Default DHCP is done at Kantech. The following steps should only be
followed if:

a) You want to configure the KT-400 with the KT-Finder, see page 33.

b) The KT-400 was communicating via the RS-232 port and you have installed a VC-485 or USB-485 to communicate via

the RS-485 port.

c) The KT-400 was communicating via a VC-485 or a USB-485 interface and you want to communicate directly with the

serial (RS-232) port.

d) You are using a KT-400 from another site and there is no communication.

How to reset the KT-400 Ethernet Four-Door Controller for Factory Default DHCP mode

Before you start:

Locate the reset button, the two jumpers JP2 - JP3 and the blue VITAL LED.

The Ethernet cable must be connected to the corporate network. The green LINK LED should lit and the yellow
TXRX LED should be flashing.

The blue VITAL LED should be flashing.

1. Remove JP2 and JP3 jumpers as described in Table 3 for Factory Default DHCP mode.

2. Press the reset button.

3. Check the blue VITAL LED heartbeat pattern.

4. Verify the IP address with the KT-Finder, see page 33.

5. Put back JP2 and JP3 jumpers.

6. Configure the KT-400 with the KT-Finder, see page 33.

Figure 13: KT-400 Factory Default Steps