Kantech KT-400 User Manual

Page 8

Advertising
background image

DN1726-0811

4

1 GB RAM

Minimum free hard disk space: 20 GB

Color depth: 24-bit (16 million colors), required for Video Integration only

Screen resolution: 1024 x 768

Graphic adapter card: 32 MB

48X CD-ROM drive

Network Interface card: 10/100 Base-T network adaptor

Note: Actual requirements may vary based on your operating system and configuration.

The Central Supervisory Equipment shall employ supply line transient protection complying with the Standard for
Transient Voltage Surge Suppressors, UL 1449, with a maximum marked rating of 330 V.

The Central Supervisory Equipment shall employ signal line Transient protection complying with the Standard for
Protectors for Data Communications and Fire Alarm Circuits, UL 497B, with a maximum marked rating of 50 V.

The Central Supervisory Equipment shall employ that communication circuits and network components
connected to the telecommunications network shall be protected by secondary protectors for communication
circuits. These protectors shall comply with the Standard for Secondary Protectors for Communications Circuits,
UL 497A. These protectors shall be used only in the protected site of the telecommunications network.

The Central Supervisory Equipment shall be installed in a temperature controlled environment. A temperature
controlled environment is defined as one that can be maintained between 13° - 35°C (55° - 95°F) by HVAC
system. Twenty-four hours on standby power shall be provided for the HVAC system. The standby power system
for the HVAC system may be supplied by an engine driven generator alone. A standby battery is not required to
be used.

A marking to identify the application and signaling function of the product is located on the inside of the unit (inner
door sticker).

For certified commercial proprietary control unit accessory applications, the requirements of UL 1076,
Commercial Proprietary Control Unit Accessory also apply.

Use Kantech part number KT-3LED-PLATE 3-color LED indicators mounted on single plate when the KT-400 is
configured with the (APOU/ALVY) KT-NCC in an EntraPass Global Edition system for remote alarm monitoring.
Refer to the KT-NCC Installation Manual, DN1611 for additional details.

The reader(s), that is(are) designated to arm or disarm the alarm system, must be within the secured side of the
customer premises.

The following Kantech readers have been validated by UL for the UL 1076 Standard: P225W26, P225KPW26,
P225XSF, P225KPXSF, P325W26, P325KPW26, P325XSF, P325KPXSF and P600.

Note: All readers can be ordered with or without the following suffixes: BEI, BEI-SE, GRY or GRY-SE.

The KT-400 Ethernet Four-Door Controller is UL 1076 listed when used with the (APOU/ALVY) KT-NCC (Network
Communications Controller).

All alarms shall be reported and acknowledged in the following priority:

Note: To set these priorities, please adjust the Event Parameters, found in EntraPass System

1. Fire alarm and industrial supervision where a risk of injury to persons, or damage or destruction of property may be

involved

2. Hold-up or panic alarm

3. Burglar alarm

4. Watchman tour (Guard tour)

5. Fire-alarm supervision

6. Burglar-alarm supervision

7. Industrial supervision where a risk of injury to persons, or damage or destruction of property will not be involved.