Wall Mounted Control Humidistat:
Wall-mounted humidistats are usually installed 4 ft. to 5 ft. above floor level. Often, the best location is
beside a thermostat that controls temperature in the same space that is to be humidified, if that loca-
tion meets the following criteria:

• The control humidistat should be located where it will be exposed to the average air condition of the

space to be humidified.

• Avoid areas of restricted air circulation, or locations where the sensor will be subjected to air drafts,

localized heat, or moisture sources.

• Locations near coffee machines, computer blower outlets, doors to other rooms, or windows that

can be opened are not suitable.

10

Modulating

High Limit

Sensor

6 - 10 Ft.

Outdoor
Temperature
Sensor

Air Flow Switch

Humidifier
Location

Main Humidity Sensor

Humidifier

Connections

Outside Air

Safety

High Limit

Humidistat

(optional)

Figure 10-1