START-UP PROCEDURE FOR ARMSTRONG SERIES EHU-700 HUMIDIFIERS

The following steps should be performed on all newly installed Series EHU-700 Humidifiers to ensure
that the humidifier and the entire humidification system functions correctly.

BEFORE TURNING ON THE POWER

Figure 14-1

1) Examine the wiring and the components

in the electrical compartment.

2) Check for any loose wires or quick-

connect terminals that may have been
pulled loose.

3) Using a screwdriver, TIGHTEN ALL

SCREW TERMINALS on the power
supply terminal block, ground lug, and
contactor (Figure 14-1).

Make sure all steam generator tank
connections are tight. Remember, a
loose joint is a HOT joint and could be a
fire hazard!

4) Locate the low voltage terminal block

(Figure 14-1).

Verify that an airflow switch is
connected between terminals 9 and 15
or that there is a jumper installed. If an
airflow switch is installed, ensure that
there is airflow.

Verify that a high limit stat is connected
between terminals 10 and 14 or that a
jumper is installed.

5) Turn on the water supply - Check for

leaks.

TURN ON POWER AT THE CIRCUIT BREAKER

6) The following should happen:

a) The Demand Mode and Tank Off lights will be illuminated. The stat demand will be

displayed.

b) If the stat demand displayed is greater than 35%, the Tank Off light will go out and a few

seconds later the Fill Light will go on. The unit will begin to fill.