Armstrong World Industries EHU-703 User Manual

Page 13

Advertising
background image

INSTRUMENT PANEL

The Mode select button is depressed for

approximately ½ second to switch both the

"display mode selected" indicator and the 3

MODE BUTTON,

digit display between:

INDICATOR, -DEMAND-

% of humidistat control range.

and DISPLAY

-CURRENT-

actual current in amps.

-% POWER-

ratio of current draw to the

nominal rating of the unit.
-DIAGNOSTIC MODE-

readout of diagnostic

codes.

Leaving the display in the diagnostic mode for 10 seconds initiates
the input/output diagnostic routine (see Diagnostics pg. 20).

The 3 digit display also exhibits a diagnostic code in the event that
the unit has shut down automatically.

FILL LIGHT

Indicates when the fill valve is energized to add water to the steam
generator.

DRAIN LIGHT

Indicates when the drain valve is energized to drain water from the
steam generator.

HIGH WATER LIGHT

Indicates that the water level in the generator has risen to the high
water level.

TANK OFF LIGHT

Indicates when power to the generator has been interrupted (tank
contactor open).

TANK ON/OFF

Depressing the tank on/off button for ½ second will open the tank
contactor. The tank off light and the diagnostic light will be on and the
display will show the message CO8. The unit will stay in this mode
until the button is pressed again.

MANUAL DRAIN

Depressing the manual drain button for ½ second will open the drain

BUTTON

valve. The tank will continue to drain until the button is pressed again.

13

DEMAND

CURRENT

% POWER

DIAGNOSTIC

FILL

DRAIN

HIGH WATER

TANK OFF

MODE SELECT

TANK ON/OFF

DRAIN ON/OFF

Advertising
This manual is related to the following products: