11.2 Extended storage

During extended storage in environments where the ambient temperature is –15 to +30 °C
(+5 to +86 °F), charge the UPS’s battery every 6 months
During extended storage in environments where the ambient temperature is +30 to +45 °C
(+86 to +113 °F), charge the UPS’s battery every 3 months.

12. Specifications

420 VA

650 VA

1000 VA

1400 VA

Acceptable input voltage

0 - 160 VAC

Input voltage (on-line operation)

92-150 VAC

Output voltage

103-132 VAC

Nominal input frequency

50 or 60 Hz, autosensing

Input Protection

Resettable circuit breaker

Frequency limits (on-line operation)

50 or 60 Hz, ±5%

Transfer time

2 ms typical, 4 ms maximum

Maximum load

420 VA 280 W 650 VA 400 W 1000 VA 670 W 1400 VA 950 W

On-battery output voltage

115 VAC

On-battery frequency

50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout.

On-battery waveshape

Stepped sine-wave

Trapezoid

Protection

Overcurrent and short-circuit protected, latching shutdown on overload.

Surge energy rating (one time,
10/1000 µs waveform)

320 J

480 J

Surge current capability (one time,
8/20 µs waveform)

6500 A maximum

Surge response time

0 ns (instantaneous) normal mode;

<5 ns common mode

Surge voltage let-through (percentage
of applied ANSI C62.41 Cat. A ±6
kV test waveform)

0.7%

0.3%

Noise Filter

Normal and common mode EMI/RFI suppression,

100 kHz to 10 MHz

Battery type

Spill proof, maintenance free, user replaceable, sealed lead-acid

Typical battery life

3 to 6 years, depending on number of discharge cycles and ambient

temperature

Typical recharge time

2 to 5 hours from total discharge