4. ELECTRICAL WIRING

4-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit

as shown on its nameplate, then carry out the wir-

ing closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and

circuit breaker for overcurrent protection should be

provided in the exclusive line.

(3) To prevent possible hazards from insulation

failure, the unit must be grounded.

(4) Each wiring connection must be done in

accordance with the wiring system diagram.

Wrong wiring may cause the unit to disorder or

become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be

very dangerous. The manufacturer will accept no

responsibility for any damage or malfunction that

occurs as a result of such unauthorized changes.

(7) Regulations on wire diameters differ from locality

to locality. For field wiring rules, must follow your

LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner

caused by electrical noise, care must be taken

when wiring as follows:

The remote control wiring and the inter-unit

control wiring should be wired apart from the

inter-unit power wiring.

Use shielded wires for inter-unit control wiring

between units and ground the shield on one side

only.

(9) If the power supply cord of this appliance is

damaged, it must be replaced by a repair shop

appointed by the manufacturer, because special-

purpose tools are required.

(10) All wiring used must be Class 1.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

You must follow LOCAL ELECTRICAL CODES for wiring.

Outdoor

Unit

Type

Time delay fuse or

circuit capacity

U-26PE1U6

30 A

U-36PE1U6

35 A

U-42PE1U6

40 A

Type

Time delay fuse or

circuit capacity

U-26PS1U6

25 A

U-36PS1U6

30 A

U-42PS1U6

35 A