7-19. Test Run Procedure

Wall mounted Type
(K1 Type)

7-20. Check Items Before the Test Run

(1) Turn ON the remote power switch at least 12 hours before the test run in order to charge the crankcase heater.

(2) Fully open the service valves on the gas-tube and liquid-tube sides.

(3) Set the sliding switches on the inside of the wireless remote controller cover to the correct settings for that model.

After changing the settings, press the RESET hole.

Check the “Check Items Before the Test Run.”

Set the indoor unit controller to “TEST.”

Return the indoor unit controller to
“NORM.” (Item 7-21-3)

NO

Is operation

possible?

Verify the combination (wiring) of indoor and
outdoor units.

Check using the Diagnosis
function table. (Refer to 7-24)

YES

Note: Check the indoor-side drainage.

(Item 7-20)

(Item 7-21-3)

Wireless remote controller transmitter

Verify that sliding switch 1 is in the “S” position.

S K N

Set sliding switch 2 to the correct setting for these models.

A: Heat pump model

(H: Heat pump, no auto heating/cooling)

C: Cooling-only model

A H C

A H C

RESET hole

Sliding switch