1. Specifications

6-5. Checking the Drainage

After wiring and piping are completed, use the follow-

ing procedure to check that the water will drain smooth-

ly. For this, prepare a bucket and wiping cloth to catch

and wipe up spilled water.

(1) Take off the tube cover and through the opening,

slowly pour about 0.3 gal of water into the drain

pan to check drainage.

(2) Do Test Run to check the drainage after complet-

ing installation. When performing Test Run, refer to

the installation instructions attached to the outdoor

unit.

(3) After drain checking is finished, return the Opera-

tion Selector switch to the RUN position (ON posi-

tion ) and remount the tube cover.

WARNING

Do not supply power to the

unit until the tubing and wir-

ing to the outdoor unit are

completed.

CAUTION

Be careful since the fan will

start turning when checking

the drainage.

WARNING

To mount the tube cover,

use 5/16" (4 × 8 mm) tap-

ping screws. Do not use long

screws as they may puncture

the drain pan and cause water

leakage.

5/16"(4

× 8 mm)

tapping screw

Tube cover

Siphon

Fig. 1-23

1

SM830203-01_PAC-i_US-letter.indb79 79

SM830203-01_PAC-i_US-letter.indb79 79