Specifications – Panasonic 36PSU1U6 User Manual

Page 97

Advertising
background image

1-91

1. Specifications

Ceiling
surface

.

x

or

p

p

A

h

c

ni

1

Suspension bolt

Washer

(supplied)

Nut
(field supply)

Fig. 1-58

Fig. 1-59

Fig. 1-60

(7) Suspend the indoor unit as follows.

(a) Mount a washer and two hexagonal nuts on

each suspension bolt as shown in Fig. 1-58.

(b) Lift the indoor unit with a lifting machine to the

ceiling surface, and place it on the washers

through the notches, to fix it in place.

(Fig. 1-59)

(c) Tighten the two hexagonal nuts on each

suspension bolt to suspend the indoor unit as

shown in Fig. 1-60.

NOTE

A ceiling surface is not always level. Please confirm

that the indoor unit is evenly suspended. For the instal-

lation to be correct, leave a clearance of about 3/8"

between the ceiling panel and the ceiling surface and

fill the gap with an appropriate insulation or filler

material.

(8) If the tubing and wiring are to go towards the rear

of the unit, make holes in the wall. (Fig. 1-61)

(9) Measure the thickness of the wall from the inside

to the outside and cut PVC pipe at a slight angle to

fit. Insert the PVC pipe in the wall. (Fig. 1-62)

Indoor
side

Outdoor
side

Fig. 1-61

Cut at slight angle

PVC pipe (field supply)

INSIDE

Wall

Slight
angle

PVC pipe

OUTSIDE

Fig. 1-62

1

SM830203-01_PAC-i_US-letter.indb91 91

SM830203-01_PAC-i_US-letter.indb91 91

2012/01/19 22:39:32

2012/01/19 22:39:32

Advertising
This manual is related to the following products: