Parameters – Atmos Energy INTERCOMBI HE32 User Manual

Page 39

Advertising
background image

39

7.3

Parameters

Parameter Setting

Factory

setting

Description

InterCombi

HE 32

Note: Appliances produced before Nov 07 had earlier version of

s/w (c not included, and d = minimum speed).

0 Service

code

[15]

-

Access to installer settings. The service code must be entered

(=15).

1

System type

0

0 = standard
1 = heating only operation + indirect hot water tank
2 = hot water only operation
3 = heating only operation

2

CH pump continuous

0

0 = pump normal with overrun
1 = pump on continuously; 2 = n/a

3

Set CH power

50

Setting maximum CH load, range c – 99% (or 100 if button
pressed again when 99 reached)

4

Set HW power

99

Setting maximum HW power, range d – 99%

5

Min. supply temperature of
the control line

25

Setting range 10°C to 25°C (Weather-dependent control)

6

Min. outside temperature of
the control line

-7

Setting range -9°C to 10°C (Weather-dependent control)

7

Max. outside temperature of
the control line

25

Setting range 10°C to 30°C (Weather-dependent control)

8

CH pump overrun time after
CH operation

1

Setting range 0 - 15 minutes

9

CH pump overrun time after
external HW tank operation

1

Setting range 0 - 15 minutes (n/a)

A

Position of three-way or two-
way valve

0

0 = output signal given for CH operation (n/a)
1 = output signal given for HW tank operation (n/a)

b

HW booster

0

(n/a)

C

Step modulation

1

0 = step modulation off during CH operation
1 = step modulation on during CH operation

c

Min fan speed in CH
operation

25

Setting range 25 to 50% (Note: For propane or for appliances
with flue non-return valve, set 40)

d

Min fan speed in HW
operation

25

Setting range 25 to 50% (Note: For propane or for appliances
with flue non-return valve, set 40)

E

Min. supply temperature
during OT demand

40

Setting range 10°C to 60°C. (OT = OpenTherm stat)

E.

OT response

1

0 = Ignore the OT demand if it is lower than parameter E
1 = Set the value at parameter E, if the OT demand is lower

2 = OT device is switched off and the room stat functions as an
on/off switch, with the supply temp set at the appliance.

F

Starting speed CH

70

Setting range 50 to 99% (Note: For propane, set 50).
This parameter sets the fan speed for ignition and post purge.

F.

Starting speed DHW

70

Setting range 50 to 99% (Note: For propane, set 50).
This parameter sets the fan speed for ignition and post purge.

h

Max. fan speed

45

Setting range 40 to 50 (40 = 4000 rpm, 50 = 5000 rpm) The
absolute maximum speed can be set through this parameter.

n

(n/a)

o

Heating delay after hw use

0

(n/a) (0 to 15 mins - must be 0 for InterCombi).

P

Minimum switch off time

during CH operation

5

Setting range 0 to 15 minutes (anti cycling function)